Holds status of input, output and relay functions ( ow totalizers will continue counting,
however). Useful during calibration to avoid false alarms and unwanted engagement of
control equipment.
Set the duration (in minutes) the channel should be held:
5 10 30 60
(in nite time, until manually released)
Manually release the channel on hold. (Appears only when a channel is held)
Hold time: min
5 10 30 60
10. Hold Inputs
Hold Input:
>
Un-Hold Input:
>
9.8 Channel Settings: If Channel Type = OTHER (4–20)
The 8058 Signal Converter allows any 4 to 20 mA signal to serve as an input signal to the 8900.
For example, a Dissolved Oxygen sensor with a 4 to 20 mA output might be connected to the 8900.
The following menu items are available ONLY when the Channel Type is "OTHER (4-20)."
The information here will appear as the full name of the channel.
NOTE: If the last character in the label is
(*), the label will be centered on the display.
If the name is less than 11 characters, an asterisk MUST be placed at the end of the
name Example: Turbidity*
Select a two-character abbreviation for the channel.
Example: DO
Set the value to be represented by 4 mA input.
Set the value to be represented by 20 mA input.
Select the decimal location for this Level display:
XXXXX. XXXX.X XXX.XX XX.XXX X.XXXX
Dampens display, output and relay response rates for this channel.
Off: Near instantaneous updates
Low: 4 s Med: 8 s Hi: 32 s
4-20mA Decimal 1
*.**** >
4-20mA Type 1:
Label1****** >
4-20mA Abbrev. 1
Ch >
4-20mA Unit 1:
Unit >
4mA Set Point 1
0.00 °C >
20mA Set Point 1
100.00 °C >
4-20mA Average 1
Med >
Select the unit of measure for this channel. Select any four characters. This selection
does not affect the measurement. It serves as a label only.