Important notices Current Transformer:
In case only one phase is to be measured, a current transformer can be connected to any socket. The other sockets
must remain empty in this "single phase" operating mode.
The individual current transformers must be connected to different phases of a three phase system. If more current
transformers are on the same phase, you will get faulty measurements.
Take particularly care that the locking of the current transformers snaps noticeably when closing.
In case the thickness of the cable is too large for the current transformer, the use is not possible at this point. Under
no circumstances the CTs shall clamped on a wire with violence.
The CT cables should not be laid parallel to 230 V/400 V lines.
The transmitter must be attached to a position where a radio link is possible, e.g, if applicable do not hang it in
cabinets with metal door.
The cable length of the CTs may not be extended.
It must be ensured that the load capacity of the sensors is not exceeded. The current transformers are designed
for a maximum of 75 A and an optimum range to 15 A..