Setting Mid-Stop Limit
MID-STOP SET
Figure 14
CAL
RUN
CROLL
CAL
RUN
CLOSE
OPEN
CAL
RUN
CAL
RUN
CRO
SET
CLEAR
SCROLL
This operator includes a programmable Mid-Stop. This feature allows the operator
to stop at a user selectable point when opening. It is used when operating very tall doors
that only open to their full height occasionally. The Mid-Stop does not effect the operator
when closing. To operate door to full open position from mid-stop, press open button again.
NOTE: Setting of the MID-STOP should only be performed AFTER Travel
Limit and Max Run Timer settings have been made.
1) Press CAL/RUN to enter calibration mode.
2) Press the CLOSE to close the door to the down limit.
3) Press SCROLL until display reads “MID-STOP
>
CLR” Figure 14.
NOTE: If the display reads MID-STOP
>
SET at this point, first clear the
MID-STOP as described below then repeat steps 1-3 and continue.
4) Press the OPEN to open the door to desired mid-stop height.
5) Press SET/CLEAR until the display reads ”
MID-STOP
>
SET”
6) Press CAL/RUN to return to run mode.
To CLEAR the Limit
1) Press CAL/RUN to enter calibration mode.
3) Press SCROLL until display reads “MID-STOP
>
SET”
5) Press SET/CLEAR until the display reads ”
MID-STOP
>
CLR”
8) Press CAL/RUN to return to run mode.
www.geniecompany.com 06-12
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
MAX RUN TMR SET
Figure 15
CAUTION:
The MID-STOP feature must be turned off in
order to properly set the Max Run Timer.
SET
CLEAR
TO RESET
1) Press CAL/RUN to enter calibration mode.
2) Press SCROLL (up or down) until display reads
”MAX RUN TMR > SET.” Figure 15.
3) Press SET/CLEAR until display reads ”MAX RUN TMR > CLR.”
4) Press CAL/RUN to return to RUN mode.
5) Cycle the door between limits.
NOTE: The Max Run Timer must be reset each and every time the Travel Limits are adjusted.
Resetting the MRT (The Max Run Timer is set automatically once the unit is cycled between Limits.
The Max Run Timer prevents the unit from running continuously in the event of a problem. The MRT’s are
set to the time required to run from one limit to the other, plus 5 seconds (nominal). When the MRT is
exceeded, the operator stops and will not respond to any command until it is reset by pressing one of the
alibration keys or by cycling power to the unit.