Owner's Manual

Medium Duty Operator
GCL-MT
www.geniecompany.com 08-12
5.4
Wall Control(s) must be located so that the door is within
sight of the user and far enough from the door, or positioned,
such that the user is prevented from coming in contact with
the door while operating the controls.
Control. Fig. 4A
.
Attach the Caution label adjacent to the Wall Con Fig. 4B.
1) For a single 3 - button installation, make connections as
shown in Fig. 4.
2) For a multiple 3 - button installations, make connections as
shown in Fig. 5.
3)
For single button accessory controls, make connections as
shown in Fig. 6.
NOTE: If an External STOP button is NOT being installed, a jumper
wire must b
e installed between the "ST
OP" AND "GND" terminals
as shown in Fig. 6.
NOTE: Long Distance Relay K
it wiring is not required for long
distanc
e control runs and should not be used
Wall Control
WARNING:
Attach the Warning placard adjacent to the Wall
trol.
Entrapment
Warning
Placard
Figure 4A
CAUTION
This door is operated by a limited-duty operator.
To prevent the motor protector from tripping,
do not exceed 15 cycles of opening
and closing per hour.
NOT FOR RESIDENTIAL USE
Figure 4B
WARNING:
If momentary contact control is to be used, a monitored
external reversing device such as a photocell system or sensing edge
switch must be used. See pages 5.6-5.7 for installation of entrapment
protection devices.
11 35
OPEN CLOSE
STOP GND -BTN
N-O
SAFETY
N-O
SAFETY
ODC
STB
ODC
STB
EXT
INTLK
EXT
INTLK
OPEN
CLOSE
STOP
3-BUTTON
STATION
CONTROL SIGNAL TERMINAL STRIP
NOTE:
JUMPER BETWEEN STOP
AND GND TERM NALS
MUST BE REMOVED
OPEN CLOSE
STOP GND -BTN
N O
SAFETY
N-O
SAFETY
ODC
STB
ODC
STB
EXT
INTLK
EXT
INTLK
OPEN
CLOSE
STOP
3-BUTTON
STATION
CONTROL SIGNAL TERMINAL STRIP
OPEN
CLOSE
STOP
3-BUTTON
STATION
NOTE:
JUMPER BETWEEN STOP
AND GND TERMINALS
MUST BE REMOVED
OPEN CLOSE
STOP GND -BTN
N-O
SAFETY
N-O
SAFETY
ODC
STB
ODC
STB
EXT
INTLK
EXT
INTLK
1-BTN
STATION
KEY
SWITCH
STATION
CARD
READER
OPEN/CLOSE
PULL
SWITCH
CONTROL SIGNAL TERMINAL STRIP
Figure 4
Figure 5
Figure 6
NOTE:
JUMPER BETWEEN
STOP AND GND
TERMINALS
MUST BE INSTALLED.