Owner's Manual

6.7
This operator includes a programmable Mid-Stop.This feature allows
the operator to stop at a user selectable point when opening. It is used
when operating very tall doors that seldom open to their full height.
The Mid-Stop does not affect the operator when closing.
1) To operate door to full open position from mid-stop, press open
button again.
NOTE: Setting of the MID-STOP should only be performed AFTER Travel
Limit and M
ax Run Timer settings have been made.
To set the Mid-Stop:
1)
Press CAL/RUN to enter calibration mode.
2) Press the CLOSE key to close the door to the down limit.
3) Press SCROLL ( ) until the display reads “MID-STOP
>
CLEAR.
Fig. 11.
NOTE: If the display reads MID-STOP
>
SET at this point, first clear the
MID-ST
OP as described below then repeat steps 1-3 and continue.
4) Press the OPEN key to open the door and release the key
when the door is at the desired Mid-Stop height.
5) Press the SET/CLEAR until the display reads “MID-STOP
>
SET.”
6) Press C
AL/RUN to return to run mode.
To clear the Mid-Sto
p:
1) Press CAL/RUN to enter calibration mode.
2) Press SCROLL ( ) until the display reads MID-STOP
>
SET.
3) Press SET/CLEAR until the display r
eads MID-STOP
>
CLR
4) Press CAL/RUN to return to run mode.
Setting the Mid-Stop
MID-STOP CLR
Figure 11
www.geniecompany.com 08-12
Medium Duty Operator
GCL-MJ&MH