Owner's Manual

STOP GND 1 BTN
N O
SAFETY
N O
SAFETY
ODC
STB
ODC
STB
EXT
INTLK
EXT
INTLK
CONTROL SIGNAL TERMINAL STRIP
Figure 7
NOTE: If External Interlock is used,THE JUMPER WIRE BETWEEN THE
EXT INTLK TERMINALS MUST BE REMOVED.
1) Optional external interlock switches are required with some
Sectional or Rolling Steel Doors to prevent the door from
operating under certain conditions including the following:
If the door is equipped with a functioning door lock, an
interlock switch must be installed to prevent electric
operation when the lock is engaged.
If the door is equipped with a pedestrian pass-through door,
an interlock switch must be installed at the pass-through
door in order to prevent electrical operation when the
pass-through door is open.
SWITCH
(N.O.)
ANGLE
STANDARD
SLIDELOCK
TRACK
SWITCH
(N.C.)
Switches must
be set in
the field.
Pass door interlock:
Should be open when
door is open.
Closed when door is
closed.
Side lock interlock:
Should be open when door is locked.
Closed when door is unlocked.
Interlock Switches
5.5
OPEN CLOSE
www.geniecompany.com 08-12
Medium Duty Operator
GCL-MJ&MH