Owner's Manual

5.1
Section 5: Wiring
Line Voltage Wiring
Fig. 1
HIGH VOLTAGE
INPUT PLUGS
LINE INPUT
TERMINALS
LINE
GROUND
ROUTE LINE VOLTAGE
WIRING IN SHADED
AREA AS SHOWN
Figure 1
L1/ 1
N/ L2
GND
LINE IN
POWER CONNECTIONS
120V
240V
LINE
(HOT)
NEUTRAL
LINE 1
LINE 2
Figure 2
WARNING
DO NOT apply power to operator until instructed to do so.
The Genie® Company recommends that line voltage
wiring be performed by a qualified electrician.
Be sure that electrical power has been disconnected from
the input power wires being connected to the operator
prior to handling these wires. An appropriate lock-out /
tag-out procedure is recommended.
Line voltage wiring must meet all local building codes.
Make sure operator voltage, phase and frequency
nameplate ratings are identical to the job site line
voltage ratings.
Input power wiring must be properly sized for the
operators amperage rating lo
cated on the nameplate.
To r
educe the risk of electric shock, make sure the chassis
of this unit is properly grounded.
1) Remove LINE VOLTAGE INPUT PLUG and install proper
fittings and 1/2"conduit.
2) Route proper LINE VOLTAGE wires into operator.
3) Locate LINE INPUT terminals on circuit board. Using
correct connectors, attach wires to LINE INPUTS, and GROUND
terminal. Fig. 2.
Keep low voltage and line voltage wires separate.
Route all line voltage wires as shown.
Plug all unused conduit holes.
www.geniecompany.com 08-12
Medium Duty Operator
GCL-MJ&MH