Owner's Manual
5.1
Section 5: Wiring
Line Voltage Wiring
Fig. 1
HIGH VOLTAGE
INPUT PLUGS
LINE INPUT
TERMINALS
LINE
GROUND
ROUTE LINE VOLTAGE
WIRING IN SHADED
AREA AS SHOWN
Figure 1
L1/ 1
N/ L2
GND
LINE IN
POWER CONNECTIONS
120V
240V
LINE
(HOT)
NEUTRAL
LINE 1
LINE 2
Figure 2
WARNING
• DO NOT apply power to operator until instructed to do so.
• The Genie® Company recommends that line voltage
wiring be performed by a qualified electrician.
• Be sure that electrical power has been disconnected from
the input power wires being connected to the operator
prior to handling these wires. An appropriate lock-out /
tag-out procedure is recommended.
• Line voltage wiring must meet all local building codes.
• Make sure operator voltage, phase and frequency
nameplate ratings are identical to the job site line
voltage ratings.
• Input power wiring must be properly sized for the
operators amperage rating lo
cated on the nameplate.
• To r
educe the risk of electric shock, make sure the chassis
of this unit is properly grounded.
1) Remove LINE VOLTAGE INPUT PLUG and install proper
fittings and 1/2"conduit.
2) Route proper LINE VOLTAGE wires into operator.
3) Locate LINE INPUT terminals on circuit board. Using
correct connectors, attach wires to LINE INPUTS, and GROUND
terminal. Fig. 2.
•
Keep low voltage and line voltage wires separate.
• Route all line voltage wires as shown.
• Plug all unused conduit holes.
www.geniecompany.com 08-12
Medium Duty Operator
GCL-MJ&MH