Owner's Manual
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
ODC STB ON
Figure 10
Monitored Reversing Devices
Safe-T-Beams® (OPTIONAL)
1) If operator is in RUN mode, press CAL/RUN key to enter calibration mode.
2) Press SCROLL key (up or down) until display reads “ ODC STB>ON” or
“ ODC STB>OFF”
Figure 10.
3) Press SET/CLEAR
key to toggle between ON and OFF.
4) Press SCROLL key (up or down)
to shift to a new function and lock setting.
5) Press CAL/RUN key to return to run mode.
WARNING: Photocell systems provide entrapment protection when
mounted near the doorway in such a way that the lower portion of an
individuals leg will break the photocell beam during normal walking
through the doorway. If an alternative mounting location is chosen, it
must be approved by the facility owner.
O N
L E
CAL
RUN
C LL
S
SET
CLEAR
SCROLL
LOSE
STOP
CAL
RUN
SC OLL
CLE R
SCROLL
LEA
6.6
NOTE: Installation of photocells or residential Monitored
Photocells DOES NOT make the unit legal for residential use. The Corporation
strictly prohibits any installation of a unit in any
residentially zoned construction.
www.geniecompany.com 0-12
Standard Duty Operator
GCL-J&H
Current UL Approved Monitored Reversing Devices:
1) MillerEdge ME and MT series monitored edge sensors used in
combination with Timer-Close Module P/N OPABTCX.S.
2) MillerEdge ME and MT series monitored edge sensors used in
combination with MillerEdge Interface Module SM-101. (Direct
connect through STB inputs).
5) Monitored Photocells P/N OPAKPEN4GX.S.
3) Residential Safe-T-Beam® Monitored Photocells from The Genie® Company,
model OSTB-BX (P/N 38176R.S).
4) Series II Safe-T-Beam® Monitored Photocells (P/N OPAKPE.S).