Owner's Manual

High Voltage Wiring
Line Voltage Wiring Fig. 1
WARNING
DO NOT apply power to operator until instructed to do so.
The Genie
®
Company recommends that line voltage wiring
be performed by a qualified electrician.
Be sure that electrical power has been disconnected from the
input power wires being connected to the operator prior to
handling these wires. An appropriate lock-out /tag-out procedure
is recommended.
Line voltage wiring must meet all local building codes.
Make sure operator voltage, phase and frequency nameplate
ratings are identical to the job site line voltage ratings.
Input power wiring must be properly sized for the operators
amperage rating located on the nameplate.
To reduce the risk of electric shock, make sure the chassis of this
unit is properly grounded.
1) Remove LINE VOLTAGE INPUT PLUG and install proper
fittings and 1/2”conduit.
2) Route proper LINE VOLTAGE wires into operator.
3) Locate LINE INPUT terminals on circuit board. Using
correct connectors, attach wires to LINE INPUTS, and GROUND
terminal.
Keep low
voltage and line voltage wires separate.
Route all line voltage wires as shown. Use liquid tight fittings
and conduit.
Plug all unused conduit holes with liquid tight plugs.
NOTE: LIQUID-TIGHT FITTINGS AND CONDUIT ARE NOT PROVIDED.
HIGH
VOLTAGE
INPUT
PLUGS
(Right
& Left)
Optional
Accessory
Modules
Optional
Additional
Transformer
LINE INPUT
TERMINALS
LINE
GROUND
208/240V 480/575V
LINE INPUT
TERMINALS
LINE
GROUND
ROUTE HIGH VOLTAGE WIRING
IN THE SHADED AREA AS SHOWN
HIGH
VOLTAGE
INPUT
PLUGS
(Right
& Left)
L1/L1
N/L2
GND
POWER CONNECTIONS
LINE IN
POWER CONNECTIONS
LINE
(HOT)
NEUTRAL
LINE 1
LINE 2
L1
L2
GND
LINE 1
LINE 2 LINE 3
L3
Three Phase
Single Phase
Optional
Additional
Transformer
115V
208V
230V
ROUTE HIGH VOLTAGE WIRING
IN THE SHADED AREA AS SHOWN
Figure 1
(SUPPLEMENT TO SECTION 5 OF THE ACCOMPANYING GCL-GH
INSTALLATION MANUAL)
1
www.geniecompany.com 06-12
Heavy Duty Operator
GCL-GH