Install Instructions

3
USA: www.GeneralFilters.com Canada: www.CGFProducts.com
Unit Location
The DH75 / DH100 dehumidiers can be installed in a variety of locations to meet the owner’s needs as
listed below. In all cases keep the following cautions in mind:
• CAUTION: The unit is designed to be installed indoors in a space that is protected from rain,
ooding and/or other forms of excess water. Unit is not designed to be exposed to chlorinated pool
conditions or spaces where unit will be exposed to corrosive chemicals or conditions.
• Install the unit with ample space as to access the lter cover panel for service and maintenance.
• Avoid discharging the air directly at people, or other areas or objects where dehydration or
evaporation of moisture is not desired.
• WARNING: If used near wet areas, be certain there is NO chance the unit could fall into the water or
be splashed and that it is wired into a GROUND FAULT INTERRUPTER protected circuit (see local
codes for other requirements).
• CAUTION: A secondary drain pan MUST be placed under the unit if installed above a living area or
above an area where water leakage could cause damage (see local codes for other requirements).
• DO NOT locate the DH75 / DH100 directly on structural members where noise or vibration may be
objectionable. The DH75 / DH100 is equipped with adjustable support feet to raise and level the unit
from the mounting surface. Ensure unit is installed level using the included bullseye level.
• In a whole house system, the DH75 / DH100 should be located near the existing air handling system
to minimize the duct work required for connection.
• When the remote control option is used, the control (dehumidistat) unit must be located in the space
that is to be conditioned. The control (dehumidistat) may be low voltage (24 volt) and should be
connected to the DH75 / DH100 with code approved, low voltage thermostat cable.
• If a remote dehumidistat is utilized, change the setting for "Remote Dehumidistat Installed" on
the control panel to "Yes".
• When locating the DH75 / DH100 in areas of extreme heat or high humidity, >120°F/90% humidity,
additional external insulation may be required to prevent undesired condensation on the exterior of
the unit.
Specifications
!
!
!
DH75 DH100
Capacity
Up To 75 Pints Per 24 Hours
@ 80°F / 27° C - 60% RH
Up To 100 Pints Per 24 Hours
@ 80°F / 27° C - 60% RH
Control LCD Touch Screen Display With Wi-Fi
Power Supply 115VAC, 60Hz 115VAC, 60Hz
Air Flow 180 CFM 220 CFM
Inlet Air Operating Temperature 50°F - 90°F / 10°C - 32°C
Filter
MERV 11 Pleated Filter
GFI #7143
10" X 12" X 1"
MERV 11 Pleated Filter
GFI #7144
12" X 12" X 1"
Duct Connections 8” Diameter (Inlet & Outlet) 10” Diameter (Inlet & Outlet)
Weight 58 Lbs. 65 Lbs.
Dimensions 12.75” H x 12.6” W x 21” L 15.75” H x 12.6” W x 21” L
Tested to ANSI/UL STD 474, and to
Canadian CSA Std C22.2 No. 92-197 and
applicable sections of ANSI/UL STD 1995.
GENERAL FILTERS
INCORPORATED