LINE DIAGRAMS PWR CELL
- 1 PWRcell Inverter - 1 CT Kit (included)
- 6 PV Links
- 2 PWRcell Batteries
This design shows a PWRcell system configured with an on-
-site generator. This design isolates the generator from the
inverter and involves a line-side tap and two transfer switches.
The inverter output supports a loads panel that can also be
transferred to the generator.
This configuration is acceptable with most utility services.
NOTE: In this configuration, the generator does not
charge PWRcell batteries or parallel with the inverter.
30A
30A
30A
30A
Power Conversion
PWRcell
TM
Inverter
Generac
PowerCore
Router
Ethernet (CAT5)
50A
Main Distribution
Panel
N
E
Automatic
Transfer
Switch
L
AC Grid
M
AC
Combiner Panel
Protected Loads Panel
Gen
N
E
L
Manual
Transfer
Switch
40A
CT (CAT5)
Storage
PWRcell Battery
PV Array
PV Optimization
PV Link
TM
Substring Optimizer
REbus
TM
DC nanogrid
Powered by REbus (DC Voltage)
AC Voltage
FOR REFERENCE ONLY; NOT FOR CONSTRUCTION.
*Installer responsible for code compliance.
*Refer to product manuals for additional installation
details and requirements.
On Site Generator / Solar + Storage
Reference Code-