Specification

2 of 2
Automatic Transfer Switches
200 Amps, Single Phase Automatic Smart Transfer Switches
Functions
All timing and sensing functions originate in the generator controller
Utility voltage drop-out...................................................................................................................................................................................................................... <65%
Timer to generator start.......................................................................................................5 second factory set, adjustable between 2-1500 seconds by a qualified dealer*
Engine warm up delay. ................................................................................................................................................................................................................. 5 seconds
Standby voltage sensor ................................................................................................................................................................................................... 60% for 5 seconds
Utility voltage pickup ......................................................................................................................................................................................................................... >80%
Re-transfer time delay ............................................................................................................................................................................................................... 15 seconds
Engine cool-down timer ............................................................................................................................................................................................................. 60 seconds
Exerciser .....................................................................................................................................................................5 minutes weekly, adjustable to bi-weekly or monthly
The transfer switch can be operated manually without power applied.
*When used in conjunction with units utilizing Evolution™ controls
Specifications
*When used with 1" Siemens or Murray Breakers
Dimensions
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2017 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 10000017069-A 6/19/17
Model RXSW200A3F
Amps 200
Voltage 120/240, 1ø
Load Transition Type (Automatic)
Open Transition
Service Rated
Enclosure Type UL Type 3R
UL Rating UL
Withstand Rating
(Amps)
10,000
22,000*
Lug Range #1 - 300 MCM Al/CU 75 C
Integrated Load Center 8
Model
RXSW200A3F
Height
(in./mm)
H1 48.0 / 1419.2
H2 42.9 / 1090
Width
(in./mm)
W1 22.5 / 571.5
W2 16.7 / 424
Depth (in./mm) 10.3 / 261.6
Depth (in./mm) 10.3 / 261.6
W1
H1
H2
W2
Depth