Installation
Automatic Transfer Switch Owner’s Manual 11
For  transfer  switches  installed  in  wet  locations,  power
cables  or  conduits  entering  above  the  level  of
uninsulated  live  parts  shall  use  fittings  listed  for  use  in
wet locations as required by 312.2 in the NEC.
NOTE: If aluminum conductors are used, apply corrosion
inhibitor  to  conductors.  After  tightening  terminal  lugs,
carefully wipe away any excess corrosion inhibitor.
Figure 3-2. Wiring Connections
Tighten terminal lugs to the torque values as noted on the
decal located  on  the  inside of  the  door. After  tightening
terminal lugs, carefully wipe away any  excess corrosion
inhibitor. 
004398
N2
E2
T2
A
T1
N1
E1
(000120)
Equipment damage. Verify all conductors are tightened 
to the factory specified torque value. Failure to do so 
could result in damage to the switch base.
CAUTION