User Manual
Table Of Contents
- Table of Contents
 - Section 1: Safety
 - Section 2: General Information
 - Section 3: Installation
 - Section 4: Operation
 - Section 5: Drawings and Diagrams
- Installation Drawing—100A SE & Non-SE/150-200A Non-SE
 - Installation Drawing—150/200A SE
 - Installation Drawing—Liquid Cooled Generator
 - Installation Drawing—Liquid-Cooled Generator
 - Installation Drawing—Air-Cooled Generator SE and Non-SE Rated ATS
 - Installation Drawing—Air-Cooled Generator SE and Non-SE Rated ATS
 
 
Installation
12 Automatic Transfer Switch Owner’s Manual
Connecting Start Circuit Wires
Control  system interconnections  consist  of  N1,  N2, and
T1, and leads 23, 0, and 194 (see Figure 3-3). 
NOTE: Generac Type TC-ER-JP power and control tray
cable  can  be  installed  as  permitted  by  the  2017  NEC.
Type  TC-ER-JP  cable  contains  color-coded  power  and
control conductors.
The generator control wiring is a Class 1 signaling circuit.
Reference  instruction  manual  of  specific  engine
generator for wiring connection details. Screw heads are
straight  bladed  and  cross-bladed,  and  should  be
tightened to 3.5 in-lb (0.4 Nm).
Recommended wire gauge sizes depend on wire length
as specified in the following chart: Consult factory if you
are operating more than one transfer switch and SACM.
Exception:  Conductors  of  AC  and  DC  circuits,  rated
1000 volts nominal, or less, shall be permitted to occupy
the  same  equipment,  cable,  or  conduit. All  conductors
shall  have  an  insulation  rating  equal  to  at  least  the
maximum circuit voltage applied to any conductor within
the equipment, cable, or conduit. See NEC 300.3(C)(1).
Connecting SACM
See Figure 3-3. The SACM can control an air conditioner
(24 VAC) directly.
Control of Air Conditioner Load
1. Route  the  thermostat  cable  (from  the  furnace/
thermostat to the outdoor air conditioner unit) to the
transfer switch.
2. Connect  the  wire  to  the  terminal  strip  terminals
(A/C  1)  on  the  SACM  as  shown  in  Figure  3-3.
These  are  normally  closed  contacts  which  open
upon load shed conditions. Route thermostat wire
away from high voltage wires.
3. If  required,  connect  additional  air  conditioners  to
the terminal strip terminals (A/C 2-4).
NOTE: These instructions are for a typical air conditioner
installation. Control of certain heat pumps and 2-stage air
conditioners may require special connections or the use
of SMMs to control the loads.
Recommended 
Wire Size
Maximum Wire Length
(One transfer switch                                         
and load shed module)
No. 18 AWG 1–115 ft (0.3–35 m)
No. 16 AWG 116–185 ft (36–56 m)
No. 14 AWG 186–295 ft (57–89 m)
No. 12 AWG 296–460 ft (90–140 m)
Contact Ratings
A/C 1-4  24 VAC, 1.0 Amp Max










