User Manual
Table Of Contents
- Table of Contents
- Section 1: Safety
- Section 2: General Information
- Section 3: Installation
- Section 4: Operation
- Section 5: Drawings and Diagrams
- Installation Drawing—100A SE & Non-SE/150-200A Non-SE
- Installation Drawing—150/200A SE
- Installation Drawing—Liquid Cooled Generator
- Installation Drawing—Liquid-Cooled Generator
- Installation Drawing—Air-Cooled Generator SE and Non-SE Rated ATS
- Installation Drawing—Air-Cooled Generator SE and Non-SE Rated ATS
Installation
10 Automatic Transfer Switch Owner’s Manual
Figure 3-1. Open Enclosure
Connecting Power Source and
Generator Power Supply
Installation and interconnection diagrams are provided in
this manual.
NOTE: All installations must comply with national, state
and local codes. It is the responsibility of the installer to
perform an installation that will pass the final electrical
inspection.
1. Connect utility supply at the utility service
disconnect circuit breaker terminals N1 and N2.
Follow torque specifications listed on the circuit
breaker.
2. See Figure 3-2. Connect utility neutral and ground
to the Upper Neutral and Ground terminals. Neutral
and Ground terminals are bonded to each other
with a jumper wire (A).
NOTE: Neutral to Ground jumper wire (A) is
provided for use if required by local codes.
3. Connect generator to the generator terminals (E1
and E2) on the transfer mechanism.
4. Connect the generator neutral wire to the lower
neutral lug.
IMPORTANT NOTE: A jumper wire (B) bonds
the upper and lower Neutral lugs. NEVER
remove this wire.
5. Connect a subpanel supply to lower T1 and T2
Terminals. Connect subpanel Neutral and Ground
to lower Neutral and Ground bars.
Conductor sizes must be adequate to handle the
maximum current to which they will be subjected, based
on the 75°C column of tables, charts, etc. used to size
conductors. The installation must comply fully with all
applicable codes, standards and regulations.
Knockouts into the transfer switch can be made in the
field as needed for entry of power cables and conduit.
Conduit entry shall maintain the proper wire bending
spaces required by Tables 312.6 (A) and (B) in the NEC.
Conduits should be arranged to provide separation
between the Utility and Generator supply conductors
inside the enclosure.
D
E
B
A
C
J
H
F
G
(000116)
DANGER
Electrocution. Turn utility and emergency
power supplies to OFF before connecting
power source and load lines. Failure to do so
will result in death or serious injury.










