Spec Sheet
2 of 2
200 Amps, Single Phase Automatic Smart Transfer Switches
Functions
All timing and sensing functions originate in the generator controller.
Utility voltage dropout ...........................................................................................................................................................................................<65%
Time to generator start .......................................................................  5 second factory set, adjustable between 2–1500 seconds by a qualified dealer*
Engine warm up delay ....................................................................................................................................................................................5 seconds
Standby voltage sensor .................................................................................................................................................................... 60% for 5 seconds
Utility voltage pickup.............................................................................................................................................................................................>80%
Re-transfer time delay ..................................................................................................................................................................................15 seconds
Engine cool-down timer................................................................................................................................................................................60 seconds
Exerciser ........................................................................................................................................ 5 minutes weekly, adjustable to biweekly or monthly
The transfer switch can be operated manually without power applied.
*When used in conjunction with units utilizing Evolution™ controls.
Specifications
Dimensions and Weight
Model RXGW20SHA3
Amps 200
Voltage 120/240, 1ø
Load transition type (automatic) Open transition service rated
Enclosure type Type 3R
Compliance ETL
Withstand rating (amps)
10,000
22,000*
Lug range #1 - 300 MCM AI/CU 75 C
Integrated load center 20–40
*When used with 1 in (25.4 mm) Siemens or Murray breakers.
Model RXGW20SHA3
Height
(in/cm)
H1 38.5 / 97.8
H2 35.0 / 88.9
Width
(in/cm)
W1 17.6 / 44.7
W2 14.0 / 35.5
Depth (in/cm) 8.0 / 20.3
Weight (lbs/kg) 45 / 20.4
®
Automatic Transfer Switches
H1
H2
W1
W2
DEPTH
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Part No. A0000053035 Rev B 06/11/19
®