Operating Guide
Operation
14 Automatic Transfer Switch Owner’s Manual
Shutting Generator Down To Perform 
Maintenance
Proceed  as  follows  to  shut  down  generator  for  mainte-
nance:
1. Press OFF button on controller.
2. Turn main utility disconnect OFF (OPEN).
3. Turn MLCB (generator disconnect) on generator to 
OFF  (OPEN)  and  follow  maintenance  proce
-
dure(s).
To turn generator back ON:
1. Turn main utility disconnect ON (CLOSED).
2. Put generator into AUTO mode.
3. Set MLCB (generator disconnect) on generator to 
ON (CLOSED).
The system is now in AUTO mode. 
Testing the SACM
A  TEST  pushbutton  is  provided  on  top  of  the  SACM  to 
test  operation  of  load  shed  functions. The TEST  button 
will work when ATS is in utility or generator position. Pro
-
ceed as follows to test the SACM:
1. Turn on utility supply to ATS.
2. Verify  managed  loads  are  powered  and  all  LEDs 
illuminate on SACM.
3. Press TEST button on the SACM.
4. Verify all of  the  connected  loads to  be “shed” are 
disabled.
5. After  five  minutes,  verify A/C  1  is  energized  and 
Status LED A/C 1 is ON.
6. After another 15 seconds, verify A/C 2 is energized 
and Status LED A/C 2 is ON.
7. After  another  15  seconds,  verify  Load  A/C  3  is 
energized and Status LED Load A/C 3 is ON.
8. After another 15 seconds, verify A/C 4 is energized 
and Status LED A/C 4 is ON.
Testing The SMM
See  SMM  owner’s/installation  manual  for  testing  proce-
dure.
Fuse Removal and Installation
See Figure 3-2. A fuse removal and installation tool (A) 
is included in the control housing.
Figure 3-2. Fuse Removal and Installation Tool
If  a  fuse  requires  replacement,  snap  tool  free  with  an 
appropriate  tool  such  as  diagonal  pliers,  and  use  it  to 
replace fuse. The tool can be stored in the control hous
-
ing retainer directly above the fuses, with the large thumb 
tab facing out.
Use  only  Generac  replacement  fuses—part  number 
100000005117, rated 240 VAC, 6.3 Amps, 10,000 AIC. 
Alternative fuses are Littelfuse
®
 021606.3MXHP or Opti-
fuse
®
 FCD-6.3.
10000004183
Rev. A
M1704
A
005450