Operation
14 Automatic Transfer Switch Owner’s Manual
Fuse Removal and Installation
See Figure 4-2. A fuse removal and installation tool (A)
is included in the control housing.
Figure 4-2. Fuse Removal and Installation Tool
If a fuse requires replacement, snap the tool free with an
appropriate tool such as diagonal pliers, and use it to
replace the fuse. The tool can be stored in the control
housing retainer directly above the fuses, with the large
thumb tab facing out.
Use only Generac replacement fuses—part number
100000005117, rated 240 VAC, 6.3 Amps, 10,000 AIC.
Alternative fuses are Littelfuse® 021606.3MXHP or
Optifuse® FCD-6.3.
T1 N1
Replace with Littlefuse 021606.3MXHP,
Optifuse FCD-6.3A or
Generac 10000005117 250 vac, 6.3A
®
®
0 GROUND
194 +12V
N1
N2
T1
23 TRANSFER
N2
004776