Product Manual
Table Of Contents
General Information
6 Automatic Transfer Switch Owner’s Manual
Utility Service Circuit Breaker (not supplied)
This switch is listed for use with the following one inch
breakers:
• Siemens*
• Murray*
• Eaton
• Square D
*Including GFCI, AFCI and tandem breakers up to 50
amps.
NOTE: For branch circuits over 50 amps, only listed
Siemens or Murray circuit breakers shall be used.
Transfer Switch Data Decal
A data decal is permanently affixed to the transfer switch
enclosure. Use this transfer switch only with the specific
limits shown on the data decal and on other decals and
labels that may be affixed to the switch. This will prevent
damage to equipment and property.
When requesting information or ordering parts for this
equipment, make sure to include all information from the
data decal.
For future reference, record the Model and Serial
numbers in the space provided on the front cover of this
manual
Transfer Switch Enclosure
The standard switch enclosure is a National Electrical
Manufacturer’s Association (NEMA) and UL 3R type. UL
and NEMA 3R (indoor/outdoor rated) type enclosures
primarily provide a degree of protection against falling
rain and sleet; are undamaged by the formation of ice on
the enclosure.
Safe Use of Transfer Switch
Before installing, operating or servicing this equipment,
read the SAFETY RULES carefully. Comply strictly with
all SAFETY RULES to prevent accidents and/or damage
to the equipment. The manufacturer recommends that a
copy of the SAFETY RULES be posted near the transfer
switch. Also, be sure to read all instructions and
information found on tags, labels and decals affixed to
the equipment.
Publications that outline the safe use of transfer switches
are the following:
• NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC
TRANSFER SWITCHES
• UL67 Panel boards
NOTE: It is essential to use the latest version of any
standard to ensure correct and current information.
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.