Spec Sheet
Functions
All timing and sensing functions originate in the generator controller.
Utility voltage dropout ...........................................................................................................................................................................................<65%
Time to generator start ....................................................................... 5 second factory set, adjustable between 2–1500 seconds by a qualified dealer*
Engine warm up delay ....................................................................................................................................................................................5 seconds
Standby voltage sensor .................................................................................................................................................................... 60% for 5 seconds
Utility voltage pickup.............................................................................................................................................................................................>80%
Re-transfer time delay ..................................................................................................................................................................................15 seconds
Engine cool-down timer................................................................................................................................................................................60 seconds
Exerciser ........................................................................................................................................ 5 minutes weekly, adjustable to biweekly or monthly
The transfer switch can be operated manually without power applied.
*When used in conjunction with units utilizing Evolution™ controls.
Specifications
Dimensions and Weight
Model RXEMW200A3
Amps 200
Voltage 120/240, 1ø
Load transition type (automatic) Open transition service rated
Enclosure type NEMA Type 3R
Compliance ETL
Withstand rating (amps) 22,000
Lug range 250 MCM - #6
Model RXEMW200A3
Height
(in/cm)
H1 30.1 / 764.3
H2 26.8 / 679.5
Width
(in/cm)
W1 13.5 / 341.8
W2 10.5 / 266.7
Depth (in/cm) 6.9 / 175.4
Weight (lbs/kg) 39.0 / 17.7
®
Automatic Transfer Switches
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2020 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Part No. A0000380921 Rev B 03/20/2020
®
H1
H2
W1
W2
DEPTH
2 of 2
200 Amps, Single Phase
PWRview Automatic Transfer Switch