Replacement Part List

2 of 2
Model RTSW100G3 RTSW100J3 RTSW100K3 RTSW200G3 RTSW200J3 RTSW200K3
Amps 100 100 100 200 200 200
Voltage 120/208V, 3Ø 120/240V, 3Ø 277/480V, 3Ø 120/208V, 3Ø 120/240V, 3Ø 277/480V, 3Ø
Load Transition Type
(Automatic)
Open Transition
Enclosure Type NEMA 3R
UL Rating Listed to UL 1008
Withstand Rating
(Amps)
14 kA 14 kA 14 kA 18 kA 18 kA 18 kA
Lug Range (Breaker) #6 AWG - 300MCM #6 AWG - 300MCM #6 AWG - 300MCM #6 AWG - 300MCM #6 AWG - 300MCM #6 AWG - 300MCM
Lug Range
(Transfer Switch)
#6 AWG - 2/O #6 AWG - 2/O #6 AWG - 2/O #4 AWG - 400MCM #4 AWG - 400MCM #4 AWG - 400MCM
Functions
Dimensions
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2016 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 10000003427-A 04/19/2016
100-200 Amps, Three Phase Automatic Transfer Switches
®
All timing and sensing functions originate in the generator controller. Parameters may vary depending on generator configuration.
Utility voltage drop-out ......................................................................................................................................................................................................................<60%
Timer to generator start ....................................................................................................5 second factory set, adjustable between 2-1500 seconds by a qualified dealer*
Engine warm up delay ......................................................................................................5 second factory set, adjustable between 5-1500 seconds by a qualified dealer*
Utility voltage pickup .........................................................................................................................................................................................................................>90%
Re-transfer time delay ...............................................................................................................................................................................................................15 seconds
Engine cool-down timer ...................................................................................................................................................... 60 seconds (5 minutes on turbo configuration)
Exerciser .............................................................................................................................................................................................................. 12 minutes every 7 days
The transfer switch can be operated manually without power applied.
Specifications
Model RTS100W RTS200W
Height (in/mm)
H1 42.91/1089.9 42.91/1089.9
H2 48/1219.2 48/1219.2
Width (in/mm)
W1 16.69/423.9 16.69/423.9
W2 21.82/554.2 21.82/554.2
Depth (in/mm) 10.06/255.5 10.06/255.5
Weight (lbs/kilos) 50/22.7 55/24.9