Item Brochure
2 of 2
Functions
Dimensions and UPC
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2014 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0L0295-A Printed in U.S.A. 12/3/14
200 Amp, Single Phase Synergy Smart Switch™
®
All Timing and sensing functions originate in the generator controller
Utility voltage drop-out ...................................................................................................................................................................... <65%, adjustable between 60 - 70%
Timer to generator start ...................................................................................................................................... 5 second factory set, adjustable between 2-1500 seconds
Engine warm up delay ................................................................................................................................................................................................................. 5 seconds
Standby voltage sensor ..................................................................................................................................................................................................65% for 5 seconds
Utility voltage pickup ........................................................................................................................................................................ >80% , adjustable between 80 - 90%
Re-transfer time delay ...............................................................................................................................................................................................................15 seconds
Engine cool-down timer ............................................................................................................................................................................................................60 seconds
Exerciser ........................................................................................................................................................... 5 minutes every 2 weeks, adjustable to weekly or monthly
The transfer switch can be operated manually without power applied.
Specifications
H2
DEPTH
H1
W2
W1
H2
DEPTH
H1
W2
W1
Model RTSI200A3 RTSB200A3
Height (in/mm)
H1 17.24/437.9 27.24/691.9
H2 20/508 30/762
Width (in/mm)
W1 12.5/317.5 11.4/289.6
W2 14.6/370.8 13.5/342.9
Depth (in/mm) 7.09/180.1 7.09/180.1
Weight (lbs/kilos) 20/9.07 39/17.69
UPC Code 696471616187 696471616170
Model RTSI200A3 (Canadian) RTSB200A3 (US)
Amps 200 200
Voltage 120/240, 1ø 120/240, 1ø
Load Transition Type (Automatic) Open Transition Open Transition Service Rated
Enclosure Type NEMA 3R NEMA 3R
UL Rating UL/CUL UL
Withstand Rating (Amps) 10,000 22,000
Lug Range 400 MCM - #4
Synergy Smart Switch™