Installation Guide
Troubleshooting/Quick Reference Guide
48 Installation Guidelines For Spark-Ignited Stationary Generators
Quick Reference Guide
To clear an active alarm, press the ENTER button twice and then press AUTO. If the alarm reoccurs, contact an IASD.
Active Alarm LED Problem Action Solution
NONE GREEN
Unit running in AUTO but 
no power in house.
Check MLCB (genera-
tor disconnect).
Check MLCB. If MLCB is ON, contact an 
IASD for assistance.
HIGH 
TEMPERATURE
RED
Unit shuts down during 
operation.
Check LED’s / Screen 
for alarms.
Inspect ventilation around generator, 
intake, exhaust, and rear of generator. If no 
obstruction, contact an IASD for assis
-
tance.
OVERLOAD 
REMOVE LOAD
RED
Unit shuts down during 
operation.
Check LED’s / Screen 
for alarms.
Clear alarm and remove household loads 
from generator. Put back in AUTO and 
restart.
RPM SENSE LOSS RED
Unit was running and 
shuts down, attempts to 
restart.
Check LED’s / Screen 
for alarms.
Clear alarm and remove household loads 
from generator. Put back in AUTO and 
restart. If generator does not start, contact 
an IASD for assistance.
NOT ACTIVATED NONE
Unit will not start in 
AUTO with utility loss.
Verify if screen says 
unit not activated.
See Activate Unit.
NONE GREEN
Unit will not start in 
AUTO with utility loss.
Check screen for start 
delay countdown.
If startup delay is greater than expected, 
contact an IASD for assistance.
LOW OIL
 PRESSURE
RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Check oil level / add oil per owners man-
ual. If oil level is correct, contact an IASD.
RPM SENSE LOSS RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Clear alarm. Check battery option in con-
trol menu. If it states battery is GOOD, con-
tact an IASD. If it states CHECK BATT-
ERY, replace battery.
OVERCRANK RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Verify fuel line shutoff valve is ON. Clear 
alarm. Attempt to start unit in MANUAL. If it 
does not start or starts and runs rough, 
contact an IASD for assistance.
LOW VOLTS 
REMOVE LOAD
RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Clear alarm and remove household loads 
from generator. Put back in AUTO and 
restart.
FUSE PROBLEM RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Inspect 7.5 amp fuse. If it is bad, replace 
with an ATO 7.5 amp fuse. If fuse is good, 
contact an IASD for assistance.
OVERSPEED RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.
UNDERVOLTAGE RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.
UNDERSPEED RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.
STEPPER 
OVERCURRENT
RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.
WIRING ERROR RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.
OVERVOLTAGE RED
Unit will not start in 
AUTO with utility loss.
Check LED’s / Screen 
for alarms.
Contact an IASD for assistance.