Installation Guide
Gaseous Fuel Systems
Installation Guidelines For Spark-Ignited Stationary Generators 27
Figure 4-5. Fuel Pressure Test Points
Final Test Procedure
The following test must be performed at startup to docu-
ment  and  validate  fuel  system  operation.  It  requires  a 
load bank connected to the unit, or a combination of load 
bank  and  system  load,  to  bring  unit to  its  full  rated  kW 
load capacity. 
Measure fuel supply pressure under each of the following 
conditions:
1. Static Pressure: Fuel supply pressure when unit is 
not  running. Must  not  exceed  maximum  pressure 
listed in the unit specification sheet.
2. Cranking  Pressure:  Fuel  supply  pressure  when 
unit is cranking. Must not drop more than 1 in water 
column (0.25 kPa) below Static Pressure or below
minimum  pressure  listed  in  the  unit  specification 
sheet. If it does, it may indicate fuel supply piping is 
not  correctly  sized,  or  primary  fuel  regulator  is 
incorrectly sized, or mounted too close to the gen
-
erator connection point. Unit may experience hard 
starting, or will not perform as expected at full load 
or during load transients.
3. Running—No Load  Pressure:  Fuel  supply  pres-
sure  when unit  is  running  at  rated  frequency  and 
voltage with  no  load. Must be  at  or slightly below 
maximum  pressure  as  listed  in  the  unit  specifica
-
tion sheet. 
4. Running—Full Load Pressure: Fuel supply pres-
sure  when  unit  is  running  with  full  rated  load 
applied (kW). Fuel supply pressure should not drop 
more  than  1–2  in  water  column  (0.25–0.50  kPa) 
from  the  Running—No Load Pressure  and  must 
NEVER drop below minimum pressure listed in the 
unit specification sheet.
A
B
C
Gauge Adapter
1/8 Inch Diameter Probe
Part No. 0K2341
009107










