Use and Care Manual
Maintenance
26 Owner’s Manual for Spark-Ignited Stationary Generators
Remove From Service
(000130)
WARNING
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
For safety, follow the steps below prior to inspection,
maintenance, or service.
IMPORTANT NOTE: If currently
experiencing a utility
outage, see Removal From Service During Utility
Outage for special instructions.
1. Open
viewing window. See Opening the Viewing
Window.
2. See Figure 5-5. Set generator MLCB (generator
disconnect) to OFF (OPEN) (A).
o
OFF
PUSH TO TRIP
C
A
B
006374
Figure 5-5. Generator Control Panel
3. V
erify both auxiliary shutdown switches are OFF
(OPEN).
4. Press
OFF on control panel (B). A red LED illumi-
nates to verify system is OFF.
5. Remove
T1 fuse from transfer switch.
6. Pull
up rubber flap (C) covering fuse holder and
remove 7.5 amp fuse.
7. Disco
nnect negative battery cable.
8. Pla
ce a DO NOT OPERATE tag or placard on both
the control panel and transfer switch.
9. If
unit has been running, wait five minutes for
engine to cool.
25 Hour Break-In
Perform the following task:
• Replace lubricating oil and oil filter.
NOTE: See Replacing Lubricating Oil and Oil Filter
under Schedule A Maintenance.
Daily Maintenance
Perform the following tasks:
• Inspect enclosure louvers.
• Inspect fuel lines.
• Inspect coolant level and hoses.
• Inspect radiator for clogging.
• Inspect lubricating oil level and drain hose.
NOTE: See Inspecting the Enclosure Louvers through
Inspecting Coolant Level and Hoses under Schedule A
Maintenance.