Specification

3of 7
®
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
RG048
120/240 V, 1Ø, 1.0 pf
48
200 48 200 200
120/208 V, 3Ø, 0.8 pf
48
167 48 167 175
120/240 V, 3Ø, 0.8 pf
48
144 48 144 150
277/480 V, 3Ø, 0.8 pf
48
72 48 72 80
operating data48 kW
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³/hr) (gal/hr) (ft³/hr) (l/hr)
RG048
Exercise cycle
25% of rated load 201 5.7 2.88 104.7 10.9
50% of rated load 336 9.5 4.16 151.3 15.7
75% of rated load 447 12.7 5.28 192 20
100% of rated load 604 17.1 6.61 240.4 25
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
RG048
120/240 V, 1Ø 100 300
120/208 V, 3Ø 118 242
120/240 V, 3Ø 97 189
277/480 V, 3Ø 63.6 122.8
Note: Fu el pipe mu st be s ize d fo r ful l l oa d.
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)
For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD
permitting purposes.
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.
There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Protector® Series