13. Press MANUAL on the control panel to start the
engine.
14. Allow the engine to run for one minute. Check for
le
aks while the engine is running.
15. Press OFF on the control panel. A red LED
illuminates
to confirm that the system is in the OFF
mode.
16. Wait ten minutes for the engine to cool and to allow
oil
to drain back to the oil pan.
17. Check oil level and add oil as necessary. See
Chec
k Lubricating Oil Level and Drain Hose.
18. Install fill cap.
NOTE: On 3
6 kW, 45 kW, and 60 kW models, open
shutoff valve to enable Lube Oil Maintainer System.
NOTE: Dispose
of used oil and oil filter at a proper
collection center.
B
A