application and engineering data
Protector™
GENERATOR OUTPUT VOLTAGE / KW–60 HZ
kW (standby) Amp (standby) kW (Prime) Amp (Prime) CB Size
RD015
120/240 V, 1Ø, 1.0 pf 15 62 12 50 70
120/208 V, 3Ø, 0.8 pf 15 52 12 42 60
120/240 V, 3Ø, 0.8 pf 15 45 12 36 50
RD020
120/240 V, 1Ø, 1.0 pf 20 83 16 67 100
120/208 V, 3Ø, 0.8 pf 20 69 16 56 80
120/240 V, 3Ø, 0.8 pf 20 60 16 48 70
RD030
120/240 V, 1Ø, 1.0 pf 30 125 24 100 150
120/208 V, 3Ø, 0.8 pf 30 104 24 83 125
120/240 V, 3Ø, 0.8 pf 30 90 24 72 100
277/480 V, 3Ø, 0.8 pf 30 45 24 36 50
SURGE CAPACITY IN AMPS
Voltage Dip @ < 0.4 pf
15% 30%
RD015
120/240 V, 1Ø 53 129
120/208 V, 3Ø 37 90
120/240 V, 3Ø 32 78
RD020
120/240 V, 1Ø 87 211
120/208 V, 3Ø 59 143
120/240 V, 3Ø 51 124
RD030
120/240 V, 1Ø 66 168
120/208 V, 3Ø 59 144
120/240 V, 3Ø 51 125
277/480 V, 3Ø 26 64
ENGINE FUEL CONSUMPTION
gal/hr L/hr
RD015
25% of rated load 0.60 2.27
50% of rated load 0.85 3.22
75% of rated load 1.10 4.16
100% of rated load 1.46 5.53
RD020
25% of rated load 0.77 2.9
50% of rated load 1.03 3.90
75% of rated load 1.46 5.53
100% of rated load 1.97 7.46
RD030
25% of rated load 0.97 3.67
50% of rated load 1.37 5.19
75% of rated load 1.97 7.46
100% of rated load 2.77 10.49