Owner’s Manual for Stationary Diesel Generators 37
Figure 5-22. Drain/Fill Coolant System
Final Instructions
1. Install left and right side access panels. See
Access Panels.
2. See Return To Service.
Schedule C Maintenance
NOTE: Perform Schedule C maintenance after 1,000
hours of service. Before proceeding below, first perform
all tasks listed under Schedule A Maintenance and
Schedule B Maintenance.
NOTE: The following procedures require special tools
and skills. Contact an IASD to perform these tasks.
Inspect Fuel Tank
Check/Adjust Fuel Injection Valve Pressure
Check/Adjust Fuel Injection Pump Timing
Adjust Intake/Exhaust Valve Clearance
Tighten Critical Fasteners
NOTE: Reset A-B-C/Year time maintenance schedule
counter using the Dealer Sub Menu (password required).
Return To Service
Proceed as follows to return unit to service after inspec-
tion, maintenance, or service of generator:
1. See Figure 5-23. Pull up rubber flap covering fuse
holder (A) and install 7.5 amp fuse.
Figure 5-23. Generator Control Panel
2. Install T1 fuse in transfer switch.
3. Verify both auxiliary shutdown switches are ON (I).
4. Press AUTO (C) on control panel. A green LED illu-
minates to verify system is in AUTO.
5. Set MLCB switch to ON (CLOSED).
6. Close viewing window.
7. Remove DO NOT OPERATE tag or placard from
both control panel and transfer switch.
8. Reset time and date.
001497
RADIATOR
DRAIN
001493
NOTE: Drain hose removed for illustration
purposes.