Product Manual
Maintenance
Owner’s Manual for Stationary Diesel Generators 29
Figure 5-6. Generator Control Panel
30 Hour Break-In
Perform the following task:
• Replace Lubricating Oil and Oil Filter
NOTE: See Replace Lubricating Oil and Oil Filter
under Schedule B Maintenance.
Daily Maintenance (If Running
Continuously)
Perform the following tasks:
• Check fuel level and fill
• Drain fuel filter
• Inspect fuel lines and hoses
• Check coolant level
• Inspect coolant hoses
• Inspect radiator for clogging
• Check lubricating oil level
NOTE: See Preliminary Instructions through Check
Lubricating Oil Level under Schedule A Maintenance.
Schedule A Maintenance
NOTE: Perform Schedule A maintenance once each
year or after 125 hours of service, whichever comes first.
Preliminary Instructions
1. See Remove From Service.
2. Remove access panels at front and both sides of
enclosure. See Access Panels.
3. Remove negative battery cable (black) from nega-
tive (-) battery terminal.
NOTE: For general location of components, see Com-
ponent Locations.
Check Fuel Level and Fill
1. See Figure 5-7. Observe fuel gauge to note level
of fuel in tank.
Figure 5-7. Check Fuel Level Gauge and Fill
2. Remove fuel fill cap from filler pipe.
3. Add fuel until needle on fuel gauge approaches the
F(ull) mark.
4. Install fuel fill cap onto filler pipe.
o
OFF
PUSH TO TRIP
006374
A
C
B
006381