Product Manual

Operation
24 Owner’s Manual for Stationary Diesel Generators
Transfer Switch Manual Operation
Prior to automatic operation, manually exercise transfer
switch to verify there is no binding or interference with
correct operation of the mechanism. Manual operation of
transfer switch is required if automatic operation fails.
IMPORTANT NOTE: Always use applicable transfer
switch owner's manual for actual manual transfer
switch operation instructions. The information pre-
sented here describes a typical V-style transfer
switch, which is not used for three phase applica-
tions.
Transfer to Generator Power
Proceed as follows to manually transfer to standby power
and start generator when utility power fails:
1. Press OFF on control panel. A red LED illuminates
to verify system is OFF.
2. Set MLCB switch to OFF (OPEN).
3. Turn off utility power supply to transfer switch using
the means provided (such as a utility MLCB).
4. See Figure 4-3. Use manual transfer handle (A)
inside transfer switch to set main contacts to
STANDBY (loads connected to standby power
source) (C).
Figure 4-3. Manual Transfer Switch Operation
(Typical)
5. Press MANUAL on control panel. Engine cranks
and starts.
6. Allow engine to run for two minutes to bring it up to
normal operating temperature.
7. Set MLCB switch to ON (CLOSED).
NOTE: V-style transfer switch not used for three-phase
applications.
Transfer Back to Utility Power
Proceed as follows to manually transfer back to utility
power and shut down generator when utility power is
restored:
NOTE: Verify utility voltage has returned and is at the
correct value.
1. Set MLCB switch to OFF (OPEN).
2. Allow engine to run for two minutes at no-load to
bring it up to normal operating temperature.
3. Press OFF on control panel to shut down engine.
4. Verify utility power supply to transfer switch is
turned off.
5. Use manual transfer handle inside transfer switch
to set main contacts to UTILITY (B) (loads con-
nected to utility power source).
6. Turn on utility power supply to transfer switch using
the means provided.
7. Press AUTO on control panel. A green LED illumi-
nates to verify system is in AUTO.
(000132)
DANGER
Electrocution. Do not manually transfer under load.
Disconnect transfer switch from all power sources
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
006375
A
B
C