Product Manual

Operation
22 Owner’s Manual for Stationary Diesel Generators
Alarm/Warning Conditions
The owner/operator is alerted to Alarm and/or Warning
conditions via the control panel LCD. All Alarm conditions
cause generator to shut down. Warning messages alert
operator to conditions that do not disable unit or require
immediate correction.
The possible Alarm/Warning messages are listed below.
NOTE: Unless correctly trained to correct and clear
Alarm/Warning conditions, contact an IASD or trained
service technician.
Change Time and Date
To change time and date after activation, see Navigation
Menu in Figure 4-2. If power is lost (battery is discon-
nected/reconnected, control panel fuse is removed/
installed, etc.), display automatically prompts user for
Time and Date. All other information is retained in mem-
ory.
Programmable Timers
Dealer Programmable
Exercise Time
A programmable exercise time is provided. In AUTO,
engine starts and runs once each week at time and day
specified. During exercise cycle, unit runs approximately
12 minutes and then shuts down. Transfer of loads to
generator does not occur unless utility power fails.
NOTE: A dealer password is required to change the
exercise time.
User Programmable
Startup Delay Timer
A programmable line interrupt delay (or startup delay)
timer is provided. When utility voltage fails (falls below
65% of nominal), the startup delay timer is started. If volt-
age rises above Utility Volts Low threshold, timer is reset.
If utility voltage remains below threshold during the dura-
tion of the timer, unit cranks and starts.
NOTE: Factory default setting is five seconds, but is
adjustable from 2 to 1500 seconds.
Warm-Up Delay Timer
A programmable warm-up delay timer is provided. As
soon as generator starts, warm-up timer starts. When
warm-up timer expires, control transfers load to genera-
tor (through transfer switch) if utility voltage is less than
80% of nominal. If utility voltage is greater than threshold
at expiration of warm-up time, load is not transferred to
the generator and a cool-down period begins. At the end
of the cool-down period, generator stops.
NOTE: Factory default setting is five seconds, but is
adjustable from 5 to 1500 seconds.
USB Port for Firmware Updates
A USB port is located beneath the rubber flap on the con-
trol panel, and is provided for firmware updates. Firm-
ware updates must be performed by an IASD.
IMPORTANT NOTE: The USB port is intended for
use with a USB thumb drive only. USB port is not
intended for charging devices such as phones or lap-
tops. Do not connect any consumer electronics to
USB port.
Alarm Messages Warning Messages
High Engine Tem-
perature
Low Coolant Level
Low Oil Pressure
Overcrank
Overspeed
RPM Sense Loss
Underspeed
Controller Fault
Ignition Fault Code
WIRING ERROR
Over Voltage
Under Voltage
Overload Remove
Load
Canbus Error
Governor Fault
Missing Cam
Pulse
Missing Crank
Pulse
Ruptured Tank
Low Fuel (10%)
E-Stop
Fuse Problem
Auxiliary Shutdown
Low Battery
Exercise Set Error
FIRMWARE
ERROR-9
Schedule A Mainte-
nance
Schedule B Mainte-
nance
Schedule C Mainte-
nance
Battery Problem
Charger Warning
Charger Missing AC
Overload Warning
Overload Cooldown
SEEPROM ABUSE
USB Warning
Download Failure
Low Fuel (20%)
Stopping…