Product Manual
Operation
20 Owner’s Manual for Stationary Diesel Generators
AUTO/MANUAL/OFF
Menu Navigation
See Figure 4-2.
Feature Description
AUTO
Activates fully automatic operation. Green LED illuminates to verify system is in AUTO. Transfer to standby
power occurs if utility power fails. Functionality of exercise timer is enabled, if set.
MANUAL
Cranks and starts engine. Blue LED illuminates to verify system is in MANUAL. Transfer to standby power
occurs if utility power fails. Functionality of exercise timer is disabled.
OFF
Shuts down engine, if running. Red LED illuminates to verify system is in OFF. Transfer to standby power
does not occur if utility power fails.
Feature Description
System Menus
HOME Screen
System returns to HOME screen if control panel is not used for five minutes. Screen normally displays a
Status message, such as Ready to Run (AUTO) or Switched to OFF (OFF), and total Hours of Protection. If
an active alarm/warning condition occurs, associated Alarm/Warning message is displayed. To clear Alarm/
Warning message, press OFF on control panel followed by ENTER. In event of multiple Alarms/Warnings,
next message is then displayed. The highest priority alarm is always displayed first.
MAIN MENU
Allows operator to navigate software using UP arrow, DOWN arrow, ENTER, and ESCAPE. MAIN MENU
can be accessed from any sub menu by consecutively pressing ESCAPE. Each time ESCAPE is pressed,
the preceding menu is displayed. The MAIN MENU is reached when System, Date/Time, Battery, and Sub
Menus are displayed.
Navigation
ESCAPE Used to abort a routine or return to preceding menu.
ENTER Used to make a selection or save an entry.
UP ARROW
DOWN ARROW
Used to move forward or backward from menu to menu or to scroll forward or backward (increment or
decrement) through available selections.
NOTE: Pressing control panel illuminates backlight for 30 seconds. The backlight also illuminates for 30 seconds whenever an
active Alarm/Warning message is displayed.