Product Manual
Activation and Startup
Owner’s Manual for Stationary Diesel Generators 17
Final Instructions
1. Use key to install side access panels.
2. Close viewing window.
NOTE: See Figure 3-9. Obtain viewing window hasp, if
not installed. With retaining tab at the bottom, insert
square end of viewing window hasp into slot below view-
ing window. Push on viewing window hasp until it snaps
in place. Gently pull on viewing window hasp to verify it
will not come free.
3. Install customer supplied padlock into viewing win-
dow hasp.
Figure 3-9. Install Viewing Window Hasp
Shutting Generator Down While
Under Load or During a Utility Outage
IMPORTANT NOTE: To avoid equipment damage,
follow these steps, in order, during utility outages.
Shutdowns may be required during utility outages to
perform routine maintenance or to conserve fuel.
To turn generator OFF:
1. Set main utility disconnect to OFF (OPEN).
2. Set generator MLCB (generator disconnect) to
OFF (OPEN).
3. Allow generator to run for cool-down for approxi-
mately one minute.
4. Set generator to OFF at the controller.
5. Remove 7.5A fuse from controller.
To turn generator back ON:
1. Install 7.5A fuse in controller.
2. Verify generator MLCB (generator disconnect) is
OFF (OPEN).
3. Set generator to AUTO mode at the controller.
4. Generator will start and run. Allow generator to run
and warm up for a few minutes.
5. Set MLCB (generator disconnect) to ON
(CLOSED).
6. Set main utility disconnect to ON (CLOSED).
The system now operates in automatic mode.
006376
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000191)
DANGER