Product Manual
Activation and Startup
Owner’s Manual for Stationary Diesel Generators 13
Open Viewing Window
1. Turn viewing window upward to access control
panel.
2. See Figure 3-6. To hold viewing window open,
remove rod from clip at back of window and insert
into hole in frame (A).
Figure 3-6. Viewing Window
Start and Run Engine
1. See Figure 3-7. Pull up rubber flap covering fuse
holder and verify installation of 7.5 amp fuse (A).
Figure 3-7. Generator Control Panel
2. Set MLCB switch down to OFF (OPEN) (B).
3. Verify both auxiliary shutdown switches are ON (I).
4. Press MANUAL (C) on the control panel to start
engine. A blue LED illuminates to verify system is
in MANUAL.
5. Allow engine to run until it reaches normal operat-
ing temperature.
6. Press OFF on the control panel to stop the engine.
A red LED illuminates to verify system is off.
Test Auxiliary Shutdown Switch
Operation
The generator is equipped with an independent means of
shutting down prime mover (engine) for use in emer-
gency situations. The shutdown mechanism, when acti-
vated, requires a mechanical reset.
See Figure 3-8. Generators 15 kW and larger are
equipped with two auxiliary shutdown switches. One aux-
iliary shutdown switch (A) is located on the generator roof
above and to the right of the viewing window. The second
auxiliary shutdown switch (B) is inside the control panel
enclosure.
Figure 3-8. Auxiliary Shutdown Switches
Test auxiliary shutdown switches after installation to ver-
ify correct operation.
1. Verify auxiliary shutdown switches are ON (I).
2. Press MANUAL key on control panel keypad to
start engine.
3. With engine running, set one auxiliary shutdown
switch to OFF (O). Engine should shut down imme-
diately.
• If engine stops, set auxiliary shutdown switch to
ON (I), clear alarm on controller, and restart engine
to verify generator is operating normally. After veri-
fying normal operation of first auxiliary switch, ver-
ify operation of second auxiliary switch.
• If engine does not stop, auxiliary shutdown
switch is not functioning correctly. Contact an
IASD.
NOTE: Auxiliary shutdown switches are not intended to
be a primary means to shut down generator under nor-
mal operating conditions. Accidental activation of an aux-
iliary shutdown switch will prevent generator from
operating during a power outage.
A
006373
o
OFF
PUSH TO TRIP
006374
B
C
A
ON
OFF
ENGINE
SHUTDOWN
004890
A
B