Product Manual

Owner’s Manual for Stationary Diesel Generators 11
Activation and Startup
Section 3: Activation and Startup
Introduction
NOTE: Before startup, unit fuel tank may need to be
inspected by the local authority having jurisdiction (AHJ)
or fire marshal to meet all requirements. User must fill
fuel tank and treat the fuel according to additive specifi-
cations.
Orientation
NOTE: The 2.2L unit is depicted in most of the artwork
used in this manual. Location and appearance of some
components may vary between engine models.
See Figure 3-1. Side of enclosure with viewing window
(A) is identified as the rear of the generator. The right and
left sides are identified by standing at rear and looking
towards front of unit. The battery (B) and fuel priming
pump (C) are located on side of unit.
Figure 3-1. Enclosure (Rear Left View)
Remove Side Access Panels
NOTE: Access panels are located at both front and sides
of enclosure.
1. See Figure 3-2. Insert key (B) into latch (A) and
turn counterclockwise one-half turn.
2. Raise panel using thumb latch.
Figure 3-2. Access Panel Key
Prime Fuel System
NOTE: The 2.2L engine is equipped with a rubber hand
priming bulb. Some 2.2L models may be equipped with a
remote stainless steel hand primer pump with a pushbut-
ton.
NOTE: The 3.4L engine primer pump and air bleed
screw are located above the fuel filter.
1. See Figure 3-3 and, if applicable, Figure 3-4.
Loosen fuel filter air bleed screw (A) and work
priming pump (B), or priming bulb, until bubbles are
observed.
Figure 3-3. Fuel Filter Air Bleed Screw
006369
A
B
C
006370
A
B
A
006188