Item Brochure

8 of 9
80 kW installation layout
Standby Generators
STUB-UP
AREA
91
[3.6]
206
[8.1]
128
[5.0]
872
[34.3]
86
[3.4]
47
[1.8]
2832
[111.5]
1777
[70.0]
51
[2.0]
68
[2.7]
1521
[59.9]
OVERALL
HEIGHT
935
[36.8]
1422 [56]
CENTER OF GRAVITY
SEE NOTE 5
WEIGHT DATA
ENGINE/KW
ENCLOSURE
MATERIAL
WEIGHT
GENSET ONLY
KG [LBS]
WEIGHT
SHIPPING SKID
KG [LBS]
SHIPPING WEIGHT
KG [LBS]
5.4L/80KW AL 925 [2035] 79 [175] 1004 [2210]
SERVICE ITEM 5.4L
OIL FILL CAP LEFT DOOR
OIL DIP STICK LEFT DOOR
OIL FILTER LEFT DOOR
OIL DRAIN HOSE RIGHT DOOR
RADIATOR DRAIN HOSE LEFT DOOR
AIR CLEANER ELEMENT EITHER DOOR
SPARK PLUGS EITHER DOOR
MUFFLER SEE NOTE 12
FAN BELT EITHER DOOR
BATTERY RIGHT DOOR
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1241 (49") WIDE 3228 (127") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2.
ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION,
BATTERY CHARGER 120 VOLT AC (.5 AMP MAX) CONNECTION AND ACCESS TO TRANSFER
SWITCH CONTROL WIRES. REMOVE FRONT COVER FOR ACCESS.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
12. REMOVE EITHER LEFT OR RIGHT HAND SIDE PANEL TO ACCESS EXHAUST MUFFLERS
AND FAN BELT.
13. FIELD CUT HOLE IS ONLY REQUIRED FOR MOUNTING OF GENERATOR ON AN EXISTING
PAD.
RADIATOR/
EXHAUST
DISCHARGE
AIR
REFERENCE OWNERS MANUAL
FOR PERIODIC
REPLACEMENT PART LISTINGS.
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
AIR INTAKE
(BOTH SIDES)
REAR VIEW
VISE ACTION LATCH,
ONE PER DOOR, TWO LIFT-OFF
DOORS PER SIDE OF GENERATOR.
RIGHT SIDE VIEW
LIFTING PROVISION (4 PLACES)
SEE NOTES 5, 8 AND
CENTER OF GRAVITY
DIMENSIONS.
FUEL LINE CONNECTION
3/4" NPT FEMALE COUPLING
LEFT SIDE VIEW
EXHAUST MUFFLERS & FAN BELT
ENCLOSED WITHIN SEE NOTE 12
CONTROL PANEL BATTERY
CHARGER IS ENCLOSED WITHIN.
FIELD CUT FOR OUTSIDE
CONDUIT CONNECTION ONLY
SEE NOTE 13
TOP VIEW
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
BATTERY 12V
GROUP 26
NEGATIVE GROUND
P/N: 058208
LOW VOLTAGE
AREA ONLY
STUB-UP AREA
SEE NOTE 4
A AA
A
A_1
Drawing #0L3178-B
DIMENSIONS: MM [INCH]