Item Brochure

3 of 9
70 • 80 • 100 • 130 • 150 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
QT070
120/240 V, 1Ø, 1.0 pf 67 292 64 267 300
120/208 V, 3Ø, 0.8 pf 70 243 67 232 300
120/240 V, 3Ø, 0.8 pf 70 211 67 201 250
277/480 V, 3Ø, 0.8 pf 70 105 67 101 125
QT080
120/240 V, 1Ø, 1.0 pf 77 333 77 333 400
120/208 V, 3Ø, 0.8 pf 80 278 80 278 300
120/240 V, 3Ø, 0.8 pf 80 241 80 240 300
277/480 V, 3Ø, 0.8 pf 80 120 80 120 150
QT100
120/240 V, 1Ø, 1.0 pf 100 417 89 371 450
120/208 V, 3Ø, 0.8 pf 100 347 94 326 400
120/240 V, 3Ø, 0.8 pf 100 301 94 283 350
277/480 V, 3Ø, 0.8 pf 100 150 94 141 175
QT130
120/240 V, 1Ø, 1.0 pf 130 542 117 488 600
120/208 V, 3Ø, 0.8 pf 130 451 122 423 500
120/240 V, 3Ø, 0.8 pf 130 391 122 367 450
277/480 V, 3Ø, 0.8 pf 130 195 122 183 225
QT150
120/240 V, 1Ø, 1.0 pf 144 625 136 567 700
120/208 V, 3Ø, 0.8 pf 150 520 142 493 600
120/240 V, 3Ø, 0.8 pf 150 451 142 427 500
277/480 V, 3Ø, 0.8 pf 150 225 142 214 250
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
QT070
120/240 V, 1Ø 129 356
120/208 V, 3Ø 194 471
120/240 V, 3Ø 168 408
277/480 V, 3Ø 83 201
QT080
120/240 V, 1Ø 174 435
120/208 V, 3Ø 186 466
120/240 V, 3Ø 161 404
277/480 V, 3Ø 70 175
QT100
120/240 V, 1Ø 150 413
120/208 V, 3Ø 186 452
120/240 V, 3Ø 161 392
277/480 V, 3Ø 107 261
QT130
120/240 V, 1Ø 236 648
120/208 V, 3Ø 364 885
120/240 V, 3Ø 315 767
277/480 V, 3Ø 161 390
QT150
120/240 V, 1Ø 486 1214
120/208 V, 3Ø 534 1334
120/240 V, 3Ø 463 1156
277/480 V, 3Ø 250 624
Standby Generators
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³/hr) (gal/hr) (l/hr) (ft
3
/hr)
QT070
Exercise cycle 110 3.1 1.2 4.6 44
25% of rated load 260 7.4 2.85 10.8 104
50% of rated load 500 14.2 5.46 20.8 200
75% of rated load 696 19.8 7.62 29.1 280
100% of rated load 1020 29 11.17 42.6 411
QT080
Exercise cycle 95 2.7 1 3.9 53
25% of rated load 549.5 15.6 6.99 1.85 126
50% of rated load 784.4 22.2 10.16 2.68 241
75% of rated load 1024.8 29.0 13.11 3.46 336
100% of rated load 1252.2 35.5 15.71 4.15 465
QT100
Exercise cycle 130 3.7 1.4 5.4 52
25% of rated load 371 10.5 4.1 15.5 149
50% of rated load 713 20.3 7.9 29.8 287
75% of rated load 991 28.2 11 41.5 400
100% of rated load 1260 35.8 13.9 52.6 507
QT130
Exercise cycle 135 3.8 1.4 5.7 55
25% of rated load 482 13.7 5.3 20 193
50% of rated load 927 26.3 10.3 38.7 373
75% of rated load 1292 36.7 14.3 54 520
100% of rated load 1786 50.8 19.8 74.6 719
QT150
Exercise cycle 155 4.4 1.7 6.5 63
25% of rated load 556 15.8 6.09 23.2 224
50% of rated load 1070 30.4 11.72 44.7 431
75% of rated load 1491 42.4 16.33 62.3 600
100% of rated load 2061 58.6 22.57 86.1 830
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply gal/hr x 90950 (LP) or ft
3
/hr x 1000 (NG).
For megajoule content, multiply l/hr x 25.35 (LP) or m³/hr x 37.26 (NG).
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.