45–70 Amps 50Hz Automatic Transfer Switches
Specifications
Features
• Single throw contactors, certified to the transfer switch standard
IEC 60947-6-1 with electrically operated, mechanically inter-
locking contacts for fast, positive connections.
• High-endurance, interlocked contactor, suitable for both induc-
tive and resistive loads.
• Less than 160 millisecond transfer time.
• Dual coil design.
• Contactors with built-in surge protection.
• Limited 5 year warranty.
Dimensions and Weight
Model PY000A000AY PY000A000B8
Rated Current (AC-1) (690V)
70A @ 40 °C
60A @ 60 °C
50A @ 70 °C
45A @ 40 °C
40A @ 60 °C
32A @ 70 °C
230V, 1Ph+N, 50Hz 400V, 3Ph+N, 50Hz
Open transition
Enclosure Type IP66
Terminal size
Power section 35mm
2
(Ph+N) 10mm
2
(Ph+N)
Control section
1.5 mm
2
Admissible Terminal Connectors
Power section
End Sleeves
Control section
Model
Height (mm) Width (mm)
Depth
(mm)
Weight
(kg)
H1 H2 W1 W2
PY000A000AY
450 500 350 400 200
12
PY000A000B8 13.5
®
50Hz Transfer Switches
H2
H1
W2
W1
DEPTH
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com