Operation Manual

General Information
33722 D MMG130DI4/175DI4/205DI4 Operating Manual 15
unit management software is loaded. It displays a live readout of the kW meter, percent of load used (gauge), selected
phase, volts and amps being produced by the generator, and the fuel level with time until empty. The controller will
automatically return to this screen from any other screen after a period of inactivity.
Figure 2-7. Home Screen
Engine Screen
The Engine screen displays the oil pressure, coolant temperature and battery voltage on three main gauges. Below
the gauges is an hour gauge displaying the total run time on the engine. At the bottom of the screen, this screen
also displays maintenance alarm status with the time remaining (black text) or the time past (red text) a scheduled
maintenance tasks, along with the description of the maintenance procedure and the action that will take place when
the timer trips the alarm.
Figure 2-8. Engine Screen
Note: If the measured value is outside the range of a gauge, the needle will not be displayed. The digital value below
the gauge will still show the measured value.
Oil Press: Displays engine oil pressure. Current coolant temperature is displayed directly below the gauge
at all times. The gauge registers oil pressure between 0-100 psi (0-689 kPa). Normal operating pressure is
between 35-80 psi (241-552 kPa).
Coolant Temp: Displays engine coolant temperature. Current coolant temperature is displayed directly
below the gauge at all times. The gauge displays coolant temperature between 150°-250°F (66°-121°C).
Normal operating temperature of the unit is between 180°-200°F (82°-93°C) with an average ambient air
temperature of 70°F (21°C).
00393
Manual Mode
3 PHASE
Volts
Amps
480
128
106.9 kW
%
0
10
100
110
20
30
40
50
60
70
80
90
Time to Empty
15 hr
Full
3/4
1/2
1/4
Empty
74
%
GEN
V
+
-
00394
GEN
V
+
-
Maintenance
Alarm Hours Description Action
1 174 To Service Oil Maintenance
2 174 To Service Fuel Maintenance
3 174 To Service Air Maintenance
Oil press. Coolant Temp. Battery
Manual Mode
Hrs
13.8 V
0
10
20 30
40
50150
170
190 210
230
250
°F214PSI50.9
100
0
20
40 60
80
0 0 3 2 5 1 5
Warning
Shutdown
Electrical Trip