Product Manual
Owner’s Manual for Mobile Generator 35
Operation
down will not create any hazards by accidentally turning
off equipment that needs to be kept on (pumps,
compressors, lights, and so forth).
1. Remove all loads from the generator by opening all
circuit breakers (turn OFF (O)).
2. Allow engine to run for approximately five minutes
to allow it to cool down.
3. Press the red engine STOP (O) button on the
controller. This will result in the generator going
into the shutdown cycle and starting a 15 second
shutdown timer. If the unit does not shut down
within 15 seconds, a stop fail alarm will be
displayed on the display screen.
4. After the unit shuts down, wait two minutes after
engine shutdown for controller actuated actions to
complete and then set the control power switch to
OFF (O).
NOTE: The ECU needs to run for 90 seconds after
shutdown to purge the DEF.
NOTE: Turning off the control panel before the controller
finishes updating could cause a loss of data.
NOTE: For extended storage time, disconnect the
battery. See the engine operator’s manual for extended
storage requirements.
Emergency Stop Switch
See Figure 3-12. The unit is equipped with one
emergency stop switch. The red button is clearly labeled
EMERGENCY STOP. The switch can be accessed and
activated with all doors closed and locked.
Figure 3-12. Emergency Stop Switch
Activate the emergency stop switch by pushing the
button in until it locks down. This trips the main circuit
breaker which then opens the contact, disconnecting the
load to the connection lugs. This will also open the fuel
circuit, shutting down the engine. The emergency stop
fault will be displayed on the control panel. The switch
will remain closed until it is pulled out.
Using the ECU Override Switch
IMPORTANT NOTE: Starting the engine with the
ECU override switch ON will not allow the engine to
shut down properly using the Engine STOP Button.
This must only be used when the engine is OFF.
The ECU override switch is located behind the controller
panel. This toggle switch powers up the ECU without
having to start the engine. Use the ECU override switch
to turn the ECU OFF. If the unit needs to be shut down
immediately, use the emergency stop switch. See
Emergency Stop Switch.
Front Hood Operation
Figure 3-13. Front Hood Operation
To Open the Front Hood
1. See Figure 3-13. With your right hand, grip the
handle located on the front panel.
2. With your left hand, pull the hood latch located on
the upper corner of the hood. Tilt the hood open
until it contacts the bulkhead panel.
CAUTION
(000246b)
Equipment Damage. The emergency stop switch is
not to be used to power down the unit under normal
operating circumstances. Doing so could result in
equipment damage.
E
M
E
R
G
E
N
C
Y
S
T
O
P
003575b
006235
CAUTION
Equipment Damage. Do not start the engine with the
Engine Control Unit (ECU) override switch ON.
Doing so will damage the ECU.
(000305)
WARNING
(000300)
Crushing Hazard. Stay clear of hood and lift
structure when opening and closing generator
hoods. Failure to do so could result in death
or serious injury.
002802