Product Manual
Owner’s Manual for Mobile Generator 29
Operation
Generator Output Connections
The installation should be in compliance with the national
electrical code (NEC), state, and local regulations.
The unit is equipped with connection lugs, located on the
lower portion of the control box behind the lug box door.
The lugs provide connection points to attach external
loads to the generator. A large decal on the inside of the
connection lug door details the proper connections for
selected voltages.
Connections to the lugs should be made by running the
power cables up through the opening in the bottom of the
box.
IMPORTANT NOTE: Do not make any connections
directly to the lugs without routing the cables
through the opening. Use a hex-wrench to tighten the
cable connections.
The connection lug door is equipped with safety interlock
switches that will trip the main circuit breaker and disable
the voltage regulator if the door is opened while the unit
is operating.
Figure 3-6. Generator Connection Lugs
A ground connection is located next to the connection
lugs. The unit must be connected to ground for proper
operating safety. The generator neutral is bonded to
ground when it is shipped from the factory. The bonding
plate must be removed when the generator is used as a
standby power source.
Generator Cam Lock
Connections (If Equipped)
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000157)
DANGER
Electrocution. Do not disable or modify the
connection box door safety switch. Doing so
will result in death or serious injury.
(000156)
DANGER
Electrocution. Before connections are made to
the unit, verify the main circuit breaker and
battery disconnect switch are OFF. Failure to do
so will result in death or serious injury.
(000155a)
WARNING
Electric shock. Only a trained and licensed electrician
should perform wiring and connections to unit. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
002822
(000156)
DANGER
Electrocution. Before connections are made to
the unit, verify the main circuit breaker and
battery disconnect switch are OFF. Failure to do
so will result in death or serious injury.
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
WARNING
Electric Shock. Verify all connections to the
cam lock receptacles are made to one row
only. Failure to do so could result in death,
serious injury, and property damage.
(000356)
(000155a)
WARNING
Electric shock. Only a trained and licensed electrician
should perform wiring and connections to unit. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.