Product Manual
Owner’s Manual for Mobile Generator 35
Operation
Fine Voltage Adjustment
See Figure 3-8. Adjust fine voltage with the fine voltage
potentiometer (A). Voltage adjustment range is ±10%.
Figure 3-8. Fine Voltage Potentiometer
Voltage Regulator
The voltage regulator controls the output of the generator
by regulating the current into the exciter field. The voltage
regulator is adjusted before shipment from the factory.
The regulator has four screwdriver adjustable
potentiometers that may be adjusted for under frequency
roll-off (U/F), U/F dip (DIP), stability (STAB), and voltage
(VOLT). Contact a GMP ASD for additional information
before attempting to adjust the voltage regulator. NOTE:
For units equipped with a Marathon DVR2000E+
automatic voltage regulator, see the Marathon operating
manual provided with the unit.
Customer Convenience
Receptacles
The unit is equipped with five receptacles. The 240/
120VAC twist-lock receptacles are rated at 50A each.
The 120VAC duplex receptacles are rated at 20A each,
with ground fault circuit interrupt (GFCI) protection. The
receptacles are not routed through the main circuit
breaker. Each receptacle has its own circuit breaker,
located directly above or next to the receptacle. Each
breaker is sized to the maximum rating of the
corresponding receptacle.
Figure 3-9. Receptacle and Breaker Locations
NOTE: Power to the receptacles is available any time
the generator is running, even if the main circuit breaker
is OFF (O). Verify equipment connected to the
receptacles is turned OFF before turning the breakers
ON (I).
NOTE: When the voltage selector switch is in position for
480/277V 3-phase, voltage at the two GFCI receptacles
is 139 volts and the voltage at the three twist-lock
receptacles is 240/139 volts. Generac Mobile does not
recommend using the receptacles in the 480V position.
When the voltage selector switch is in position for 208/
120V 3-phase, voltage at the three twist-lock receptacles
and the two GFCI receptacles is 208/120 volts.
A
011136
CAUTION
(000303)
Equipment Damage. Verify voltage application
before making changes to factory settings. Incorrect
voltage applied to a load could result in equipment
damage.
A 20 A circuit breakers
B 50 A circuit breaker (3 locations)
C 120/240 V twist-lock receptacle (3 locations)
D 120 V GFCI receptacle (2 locations)
004866
A
B
C
D










