34 Owner’s Manual for Mobile Generator
Operation
5. Connect electrical harness, provided with external
DEF tank, to bulkhead connector (D).
6. Switch the system enable switch (C) to ON.
NOTE: Fluid level in each on-board tank determines
when the respective pump switches on and off.
NOTE: When external tanks are not connected, the
system enable switch (C) should be switched to OFF,
preventing fuel pump activation and controller faults.
NOTE: If faults occur, reset the system by switching the
system enable switch (C) OFF and ON.
AUTO Exercise Timer
The controller is capable of starting and stopping the unit
automatically, based on a programmable schedule.
Units installed in a standby application should be
exercised regularly to maintain operating condition and to
ensure responsiveness in an emergency situation.
Proceed as follows to operate the unit in AUTO mode:
Accessing the Configuration Menu
1. With the unit stopped, press ▲, ►, ▼, or ◄ to
navigate to the maintenance screens from any of
the operator screens.
2. While on any maintenance screen, press and O
simultaneously. The controller will display the
Configuration menu.
3. To save any changes and exit the Configuration
menu, press and hold for five seconds. To cancel
any changes and return to the maintenance
screen, press and hold O for five seconds.
Set the Controller Clock
The schedule runs based on the time set in the controller
clock. Proceed as follows to set the controller clock
before setting the schedule:
1. Navigate to the maintenance group and press ► to
access it.
2. Press ► to select the time section.
3. Set the time and date to the correct local time.
Set the Schedule
NOTE: The controller must be in AUTO mode to run at
the programmed time. Use a trickle or solar battery
charger to prevent the controller from draining the battery
while in AUTO mode.
1. Access the scheduler group by pressing the ►
button.
NOTE: The scheduler group consists of the scheduler
options and scheduler setup sections. Each section can
be accessed and exited using the ► and ◄ buttons.
2. Access the scheduler options section. Within this
section, the scheduler can be enabled, run mode
selected, and load mode selected.
3. Access the scheduler setup section. In this section,
each schedule entry can be modified by pressing
the button to select the item, and the ▲ and ▼
buttons to define them.
NOTE: If setting up a daily scheduled run, select Weekly
Run Mode, then set start time and duration for each day
(seven schedule entries total). This will repeat the seven
day schedule as long as the unit is in AUTO mode.
Setting Up a Daily Scheduled Run
1. Enable the scheduler.
2. Set RUN mode to Weekly.
3. Set load to preferred method.
4. Set the start time and duration for seven days
(Monday–Sunday).
5. Set the controller to AUTO mode.
Set the Unit to AUTO Mode
From any operator or maintenance screen, press and
hold the AUTO or MANUAL mode ( ) button for five
seconds, or until AUTO mode is displayed at the top of
the screen.
NOTE: If any of the scheduled time slots are currently
active, the controller will begin the starting sequence and
start the unit, provided there are no shutdown conditions
present.
Shutting Down the Unit
Prior to shutting down the unit, check with personnel
using power supplied by the generator and let them know
the power is going to be turned off. Verify the power shut
Item Values
Enable Yes, No
Run Mode Monthly, Weekly
Load Idle, In Island, On Load, Off Load
Item Values
Schedule Entry 1–16
Start Time 00:00–23:59
Duration 00:00–99:59
Day Monday–Sunday
Week (of month) First, Second, Third, Fourth