Product Card

3 of 4
Generator
Model G007047-1 (8 kVA) G007048-1 (10 kVA) G007049-1 (13 kVA)
Rated Maximum Continuous Power Capacity (LP) 8,000 VA* 10,000 VA* 13,000 VA*
Rated Maximum Continuous Power Capacity (NG) 7,000 VA* 10,000 VA* 13,000 VA*
Rated Voltage 220 220 220
Rated Maximum Continuous Load Current – 220 Volts (LP/NG) 36.4/31.8 45.5/45.5 59.1/59.1
Main Line Circuit Breaker 40 Amp 50 Amp 63 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 50 Hz 50 Hz 50 Hz
Power Factor 1.0 1.0 1.0
Battery Requirement (not included) 12 Volts, Group 26R 540 CCA Minimum or Group 35AGM 650 CCA Minimum
Unit Weight (lb/kg) 341/155 389/176 425/193
Dimensions (L x W x H) in/mm 48 x 25 x 29/1218 x 638 x 732
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load** 62 64 64
Sound output in dB(A) at 23 ft (7 m) with generator exercising five minutes at low speed ** 54 55 55
Engine
Type of Engine GENERAC G-FORCE 500 SERIES GENERAC G-FORCE 1000 SERIES GENERAC G-FORCE 1000 SERIES
Number of Cylinders 2 2 2
Displacement 530 cc 999 cc 999 cc
Cylinder Block Aluminum w/ Cast Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state w/ Magneto Solid-state w/ Magneto Solid-state w/ Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 VDC 12 VDC 12 VDC
Oil Capacity Including Filter 1.7 qt/1.6 L 1.9 qt/1.8 L 1.9 qt/1.8 L
Operating rpm 3,000 3,000 3,000
Fuel Consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid Propane ft
3
/hr (gal/hr) [l/hr]
1/2 Load
Full Load
93 (2.63)
153 (4.33)
35 (0.96) [3.62]
56 (1.55) [5.87]]
126 (3.57)
204 (5.78)
45 (1.24) [4.70]
70 (1.91) [7.24]
150 (4.25)
231 (6.54)
51 (1.40) [5.29]
80 (2.20) [8.32]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5-7" water column (7-13 mm mercury) for natural gas, 10-12" water column
(19-22 mm mercury) for LP gas.
Outputs are based upon values @ 1000 BTU per cubic feet with NG and 2500 BTU per cubic feet with LP
@ 37.26 Megajoules per cubic meter with NG and 93.15 Megajoules per cubic meter with LP
Controls
Two-Line Plain Text Multilingual LCD Display Simple user interface for ease of operation.
Mode Buttons:Auto Automatic Start on Utility failure. Programmable exercise.
Manual Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages Standard
Engine Run Hours Indication Standard
Programmable start delay between 2-1500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable (Brownout Setting) From 140-156 V/175-198 V
Future Set Capable Exerciser/Exercise Set Error Warning Standard
Run/Alarm/Maintenance Logs 50 Events Each
Engine Start Sequence Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter Lock-out Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC Warning Standard
Low Battery/Battery Problem Protection and Battery Condition Indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Under-Frequency/Overload/Stepper Overcurrent Protection Standard
Safety Fused/Fuse Problem Protection Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring Protection Standard
Common External Fault Capability Standard
Field Upgradable Firmware Standard
®
8/10/13 kVA
specifications
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying emergency power for the duration
of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum kilovolt amps and current are subject to and limited by such factors as fuel Btu/megajoule
content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6 °C (10 °F) above 16 °C (60 °F).
8/10/13 kVA