Installation Guide
Quick Reference Guide
48 Installation Guidelines For Australian 50 Hz Air-Cooled Generators
UNDERSPEED RED
Unit will not start in
AUTO with utility loss.
Check the LEDs /
Screen for alarms.
Contact an IASD.
STEPPER
OVERCURRENT
RED
Unit will not start in
AUTO with utility loss.
Check the LEDs /
Screen for alarms.
Contact an IASD.
MISWIRE RED
Unit will not start in
AUTO with utility loss.
Check the LEDs /
Screen for alarms.
Contact an IASD.
OVERVOLTAGE RED
Unit will not start in
AUTO with utility loss.
Check the LEDs /
Screen for alarms.
Contact an IASD.
LOW BATTERY YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
MENU option from the MAIN MENU. If
battery condition displays GOOD, contact
an IASD. If control panel displays CHECK
BATTERY, replace the battery.
BATTERY
PROBLEM
YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Contact an IASD.
CHARGER
WARNING
YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Contact an IASD.
CHARGER
MISSING AC
YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Contact an IASD.
SERVICE A YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Perform SERVICE A maintenance. Press
ENTER to clear.
SERVICE B YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Perform SERVICE B maintenance. Press
ENTER to clear.
INSPECT
BATTERY
YELLOW
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Inspect battery. Press ENTER to clear.
Table 9-1. System Diagnosis (Continued)
Active Alarm LED Problem Things to Check Solution