Installation Guide

Troubleshooting
46 Installation Guidelines For Australian 50 Hz Air-Cooled Generators
No transfer to
standby after
utility source
failure
MLCB (generator disconnect) is OFF (OPEN). Reset generator disconnect to ON (CLOSED).
Defective transfer switch coil. Contact an IASD for assistance.
Defective transfer relay. Contact an IASD for assistance.
Transfer relay circuit open. Contact an IASD for assistance.
Defective control logic board. Contact an IASD for assistance.
Engine may be warming up.
Refer to Cold Smart Start.
Check the controller screen to verify status.
Unit consumes
large amounts of
oil
Excessive engine oil. Adjust oil to proper level.
Defective engine breather. Contact an IASD for assistance.
Improper type or viscosity of oil.
See Engine Oil Requirements in the Owner’s
Manual.
Damaged gasket, seal, or hose. Check for oil leaks.
Restricted air filter. Replace air filter.
* Contact an IASD for assistance.
Problem Cause Correction