Installation Guide

Fuel Conversion / Gas Connections
28 Installation Guidelines For Australian 50 Hz Air-Cooled Generators
Checking Gas Line Connections
Check Gas Pressure
1. Check gas pressure at the regulator in the
generator by following these steps.
Close gas supply valve.
See Figure 5-7. Remove the top gas pressure test
port from the regulator and install the gas pressure
tester (manometer).
Figure 5-7. Checking Pressure with Manometer
Open the gas supply valve and verify the pressure
is within the specified values.
Record static gas pressure:
NOTE: Gas pressure can also be tested at the fuel shut-
off valve shown in Figure 5-2 if the valve is equipped with
a manometer port.
NOTE: See the owner’s manual or the spec sheet for
proper fuel pressure specifications. If the gas pressure is
not within specifications, contact the local gas supplier.
2. Close gas valve when completed. Keep manome-
ter connected for future tests of the generator while
starting, running, and under loads.
Perform Leak Test
All products are tested at the factory before shipping to
ensure the performance and integrity of the fuel system.
However, it is important to perform a final fuel system
leak test before starting the generator. The entire fuel
system should be tested from supply to regulator.
See Figure 5-8. Perform a final fuel system leak test
after generator installation. The test will identify possible
leaks at all connection points (A).
It is best practice to perform a fuel system leak test
during normally-scheduled maintenance.
Figure 5-8. Connection Points to Leak Check
Check for leaks by spraying all connection points with a
non-corrosive gas leak detection fluid. The solution
should not be blown away or form bubbles.
006095
(000192)
DANGER
Explosion and fire. Fuel and vapors are extremely
flammable and explosive. No leakage of fuel is
permitted. Keep fire and spark away. Failure to do
so will result in death or serious injury.
A
A
A
005808