Installation Guide
Site Selection and Preparation
14 Installation Guidelines For Australian 50 Hz Air-Cooled Generators
Figure 3-3. Compacted Soil or Gravel Pad
NOTE: If a concrete pad is required, follow all applicable
federal, state, or local codes.
Transportation Recommendations
Use a suitable cart or equipment to carry the generator,
including the wooden pallet, to the installation site. Place
cardboard between the hand cart and the generator to
prevent any damage or scratches to the generator.
IMPORTANT NOTE: Do not lift, carry, or move the
generator by grasping the louvers. Doing so may
bend or damage the sheet metal.
Placement on Roofs, Platforms,
and Other Supporting Structures
Where required to place the generator on a roof, plat-
form, or other supporting structure, like a deck, the gen-
erator shall be placed in accordance with the
requirements in NFPA 37, Section 4.1.3. The generator
can be located 45.7 cm (18 in) from structures having
combustible walls and 1.52 m (5 ft) from any operable
opening in the structure. The surface beneath the gener-
ator and beyond shall be noncombustible to a minimum
distance of 30.5 cm (12 in). Consult with the local Build-
ing Inspection Department or Fire Department to deter-
mine which noncombustible materials are approved for
installation.
A
B
000856