Technical Specifications
1 of 2
®
Smart Management
Module (SMM)
Smart Management
Module (SMM)
Model: G007000-0
UPC: 696471070002
GENERAC
®
LOAD MANAGEMENT
50 Amp Smart Management Module (SMM)
FEATURES
Generac's Smart Power Management System is designed to optimize the performance of a standby generator. The system can consist of up to eight individual Smart
Management Modules (SMM). Unlike other load management systems that depend on another control device, the SMM’s are self-aware and operate autonomously.
Frequency is the true measure of generator engine performance, and does not need to factor in increased ambient temperatures, elevation changes, or generator fuel
type. The SMM monitors the frequency (Hz) of the power being produced by Generac’s standby generators. If frequency falls below a certain threshold of a correctly
sized system, the SMM will automatically shed the managed loads to allow the generator to recover.
The modules can be set to a load priority between 1–8, or be set in a lock-out only mode for loads that do not need to run in an outage. This reduces the minimum size
of generator required for a more cost-effective solution.
* It is recommended to size the generator with appropriate excess capacity to allow starting of the largest managed loads (i.e. loads with highest starting currents). Each
managed load of the SACM and SMM must be assigned a unique priority setting, so no two managed loads attempt to start simultaneously. See owner’s manual for
more information.
SMM SPECIFICATIONS
Power supply source ................................................................................................................................................................................... 240 VAC (from line input)
Contact voltages............................................................................................................................................................................................................. 220/240 VAC
Contactor coil voltage............................................................................................................................................................................................................ 240 VAC
Coil VA inrush .................................................................................................................................................................................................................................30
Coil VA sealed................................................................................................................................................................................................................................6.5
Poles ................................................................................................................................................................................................................................................2
Resistive amps................................................................................................................................................................................................................................50
F/L Inductive amps..........................................................................................................................................................................................................................40
Locked rotor amps.........................................................................................................................................................................................................................180
NEMA .............................................................................................................................................................................................................................................3R
Enclosure rating .........................................................................................................................................................................................................................UL 50
Frequency selectability...................................................................................................................................................................................................50 Hz / 60 Hz